XGN66-12 (Z) box type fixed AC metal enclosed switchgear

XGN66-12 (Z) box type fixed metal AC enclosed switchgear (hereinafter referred to as switchgear) is a complete set of indoor three-phase AC 50Hz, rated voltage 3.6-12kV, rated current 630A~3150A single bus sectionalized system, which is used to receive and distribute electric energy and control, protect and monitor the circuit. It can meet the use requirements of various types of power plants, substations (switching stations) and industrial and mining enterprises.

Keyword:

Switch cabinet Metal AC Fixed

Classify:

Inquiry:

Product introduction

◆ Product overview

XGN66-12 (Z) box type fixed metal AC enclosed switchgear (hereinafter referred to as switchgear) is a complete set of indoor three-phase AC 50Hz, rated voltage 3.6-12kV, rated current 630A~3150A single bus sectionalized system, which is used to receive and distribute electric energy and control, protect and monitor the circuit. It can meet the use requirements of various types of power plants, substations (switching stations) and industrial and mining enterprises.
The switchgear meets the requirements of IEC60298, GB3906, DL/T402, DL/T404 and other standards, and has a reliable "five prevention" locking function. It can be equipped with ZN21, VSI, ZN66, ZN28 or other types of vacuum circuit breakers with strong compatibility, elegant appearance and convenient maintenance. It is a power distribution device with superior performance.

◆ Environmental conditions for normal use

1. The ambient air temperature shall not be higher than+40 ℃ and not lower than - 10 ℃. The average temperature within 24 hours shall not exceed+35 ℃;

2. The daily average relative humidity of the surrounding environment shall not exceed 95%, and the monthly average relative humidity shall not exceed 90%;

3. The altitude of the place of use shall not exceed 1000m;

4. The maximum seismic intensity shall not exceed 8 degrees;

5. The switch cabinet shall be installed in an indoor place without fire, explosion, serious pollution, chemical corrosion gas and severe vibration;

6. When the equipment is installed, the inclination to the vertical plane shall not exceed 5 °.

Note: If the above normal use conditions are exceeded, users can coordinate with our company to solve the problem.

◆ Product features

1. Vacuum circuit breaker is used as the main switch, with less maintenance, no pollution and long service life;

2. Strengthen insulation. Air electrical clearance ≥ 125mm, creepage distance of porcelain insulator ≥ 210mm, creepage distance of resin insulator ≥ 230mm, and condensation frost on insulation surface for a short time will not affect its insulation level;

3. The electrified body is sealed in the metal shell, and the main busbar between cabinets is supported by insulating sleeve and used as the cabinet enclosure;

4. The overall dimension is small. The basic skeleton is 2750mm high, 1000mm wide and 1200mm deep.

◆ Ordering instructions

1. Number, purpose and single line system diagram of main wiring scheme; Rated voltage and current; Rated short-circuit breaking current; Layout plan of power distribution room and arrangement diagram of switch cabinet;

2. Specifications and incoming/outgoing methods of incoming/outgoing cables;

3. Secondary function diagram and terminal arrangement diagram shall be prepared by our company if there is no terminal arrangement diagram;

4. Model, specification and quantity of electrical components of switch cabinet;

5. Summary sheet of electrical equipment;

6. When bus bridge is required, span and height dimensions shall be provided;

7. The switch cabinet shall be put forward when ordering under special environmental conditions;

8. When other accessories and spare parts are needed or exceeded, the type and quantity shall be proposed.

Related Products

YBW series high/low voltage prefabricated substation (European type substation)


YBW-12 series prefabricated substations are characterized by strong completeness, small size, compact structure, safe and reliable operation, convenient maintenance, and mobility.

ZB series combined substation (American type substation)


ZB series American box transformer is a new type of power distribution equipment, which is used to install transformers, high-voltage load switches and high-voltage current limiting fuses in the transformer tank for insulation and cooling with mineral oil. The utility model has the advantages of reasonable and compact structure, small volume, flexible installation, convenient operation, small floor area, etc.

ZW7-40.5 outdoor high-voltage vacuum circuit breaker


ZW7-40.5 series outdoor high-voltage vacuum circuit breaker is three-phase AC 50Hz outdoor high-voltage electrical equipment; It is applicable to the control and protection of 20~40.5kV power transmission and distribution system; It can also be used for connecting circuit breakers and opening and closing capacitor banks; This product, together with the recloser, can realize the intelligent sectional reclosing control of the power system. The current transformer can be attached for measurement and protection.

ZW8-12 Outdoor Intelligent High Voltage Pole mounted Circuit Breaker


ZW8-12 series outdoor high-voltage vacuum circuit breaker is a high-voltage outdoor switchgear with rated voltage of 12KV and three-phase AC 50Hz, which is mainly used to break and close the load current, overload current and short circuit current of rural power grid, urban power grid and small power system. The overall structure of the product is three-phase box type. The three-phase vacuum arc extinguishing chamber is placed in a metal box. The SMC insulation material is used for phase to phase insulation and ground insulation. The product has reliable performance and high insulation strength. It is a new generation of oil-free products for urban and rural power grids.

ZW20-12 Outdoor High Voltage Pole mounted Circuit Breaker


When there is a fault in the T-connected branch line of 10KV overhead distribution line or the end user, the outgoing switch of the substation will trip because the protection action time limit of the incoming switch cannot be reasonably adjusted in coordination with the protection time limit of the outgoing switch of the substation. If the fault is permanent and the substation reclosing will not be successful, a local accident within the medium voltage user boundary will cause the power failure of the entire 10KV distribution line.

FZW28-12 Outdoor High Voltage Pole mounted Circuit Breaker


FZW28-12 outdoor boundary vacuum load switch is used in column installation, with manual and electric operation functions. The switch body adopts VSP5-12 imported from Toshiba, Japan. The switch is a maintenance free load switch. Vacuum arc extinguishing and SF6 gas are used as insulation medium to ground and between phases. It is applicable to substations, industrial and mining enterprises, urban and rural power grids as protection cities, rural power grid automation distribution networks and places with frequent operations.

Obtain product quotation